NZS 1170.5:2004 (Excl. A1) Structural Design Actions - Part 5: Earthquake design actions - New Zealand - Sponsored.
- Abbreviation
- NZS 1170.5:2004 (Excl. A1)
- Valid from
- 21/12/2004
- Information provider
- Standards New Zealand,
- Author
- Standards New Zealand
- Information type
- New Zealand Standard,
- Format
- PDF, HARD COPY,
Description
This Standard provides procedures for the determination of earthquake actions on structures in New Zealand.
It gives the requirements for verification procedures, site hazard determination, the evaluation of structural characteristics, structural analysis for earthquake action effects, the determination and limits for deformations and the seismic design of parts of structures. It is to be applied in conjunction with AS/NZS 1170 parts 0, 1, 2 and 3.
Appendices cover aspects of ultimate limit state design and the requirements for material specific structural design standards that are able to be used in conjunction with NZS 1170.5.
This standard is used by structural engineers to assess and calculate the forces and deformations from earthquakes acting on structures such as buildings and other structures. It helps engineers design structures that comply with the New Zealand Building Code’s earthquake resistance requirements.
Scope
This Standard, NZS 1170.5, sets out procedures and criteria for establishing the earthquake actions to be used in the limit state design of structures and parts of structures within New Zealand that are within the scope of AS/NZS 1170.0. The design of the following structures for earthquake actions is outside the scope of this Standard:
- (a) Bridges;
- (b) Tanks containing liquids;
- (c) Civil structures including dams and bunds;
- (d) Offshore structures that are partly or fully immersed; and
- (e) Soil retaining structures.
This Standard does not address the effects of slope instability, liquefaction, fault displacement, seiche and/or tsunami resulting from earthquake shaking. This Standard is to be used in conjunction with material specific structural design Standards that comply with the requirements of Appendix D.
This resource is cited by:
NZS 1170.5:2004 (Excl. A1) Structural Design Actions - Part 5: Earthquake design actions - New Zealand - Sponsored.
This document is CITED BY:
-
G10/AS1 (First Edition, Amendment 6)
NZS 1170.5:2004 (Excl. A1) is cited by Acceptable Solution G10/AS1: Piped Services from 30/09/2010
-
G12/AS2 (Third Edition, Amendment 10)
NZS 1170.5:2004 (Excl. A1) is cited by Acceptable Solution G12/AS2: Solar Water Heaters from 1/12/2007
-
G12/AS2 (Amd 14) (Third Edition, Amendment 14)
NZS 1170.5:2004 (Excl. A1) is cited by Acceptable Solution G12/AS2: Solar Water Heaters from 1/12/2007
-
G12/AS2 (Amd 13) (Third Edition, Amendment 13)
NZS 1170.5:2004 (Excl. A1) is cited by Acceptable Solution G12/AS2: Solar Water Heaters from 1/12/2007
-
G12/AS2 (Amd 12) (Third Edition, Amendment 12)
NZS 1170.5:2004 (Excl. A1) is cited by Acceptable Solution G12/AS2: Solar Water Heaters from 1/12/2007
-
G12/AS2 (Third Edition, Amendment 11)
NZS 1170.5:2004 (Excl. A1) is cited by Acceptable Solution G12/AS2: Solar Water Heaters from 1/12/2007
-
G12/AS2 (Third Edition, Amendment 7)
NZS 1170.5:2004 (Excl. A1) is cited by Acceptable Solution G12/AS2: Solar Water Heaters from 1/12/2007
-
G12/AS2 (Third Edition, Amendment 8)
NZS 1170.5:2004 (Excl. A1) is cited by Acceptable Solution G12/AS2: Solar Water Heaters from 1/12/2007
-
G12/AS2 (Third Edition, Amendment 9)
NZS 1170.5:2004 (Excl. A1) is cited by Acceptable Solution G12/AS2: Solar Water Heaters from 1/12/2007
-
B1/VM1 (Amd 17) (First Edition, Amendment 17)
NZS 1170.5:2004 (Excl. A1) is cited by Verification Method B1/VM1: Structure - General from 19/05/2011
-
B1/VM1 (Amd 15) (First edition, amendment 15)
NZS 1170.5:2004 (Excl. A1) is cited by Verification Method B1/VM1: Structure - General from 19/05/2011
-
B1/VM1 (Amd 13) (First edition, Amendment 13)
NZS 1170.5:2004 (Excl. A1) is cited by Verification Method B1/VM1: Structure - General from 19/05/2011
-
B1/VM1 (Amd 10) (First edition, Amendment 10)
NZS 1170.5:2004 (Excl. A1) is cited by Verification Method B1/VM1: Structure - General from 19/05/2011
-
B1/VM1 (Amd 16) (First edition, Amendment 16 )
NZS 1170.5:2004 (Excl. A1) is cited by Verification Method B1/VM1: Structure - General from 19/05/2011
-
B1/VM1 (Amd 11) (First Edition, Amendment 11)
NZS 1170.5:2004 (Excl. A1) is cited by Verification Method B1/VM1: Structure - General from 19/05/2011
-
B1/VM1 (Amd 14) (First edition, Amendment 14)
NZS 1170.5:2004 (Excl. A1) is cited by Verification Method B1/VM1: Structure - General from 19/05/2011
-
B1/VM1 (Amd 12) (First Edition, Amendment 12.)
NZS 1170.5:2004 (Excl. A1) is cited by Verification Method B1/VM1: Structure - General from 19/05/2011
-
B1/VM1 (Amd 21) (First Edition, Amendment 21)
NZS 1170.5:2004 (Excl. A1) is cited by Verification Method B1/VM1: Structure - General from 19/05/2011
-
B1/VM1 (Amd 20) (First edition, Amendment 20)
NZS 1170.5:2004 (Excl. A1) is cited by Verification Method B1/VM1: Structure - General from 19/05/2011
-
B1/VM1 (Amd 19) (First edition, Amendment 19)
NZS 1170.5:2004 (Excl. A1) is cited by Verification Method B1/VM1: Structure - General from 19/05/2011
-
B1/VM1 (Amd 18) (First Edition, Amendment 18)
NZS 1170.5:2004 (Excl. A1) is cited by Verification Method B1/VM1: Structure - General from 19/05/2011
-
AS/NZS 1170.0:2002
NZS 1170.5:2004 (Excl. A1) is cited by AS/NZS 1170.0:2002 Structural Design Actions - General principles
-
AS/NZS 2327:2017
NZS 1170.5:2004 (Excl. A1) is cited by AS/NZS 2327:2017 Composite structures - Composite steel-concrete construction in buildings
-
AS/NZS 4600:2005
NZS 1170.5:2004 (Excl. A1) is cited by AS/NZS 4600:2005 Cold-formed steel structures
-
CCANZ CP 01:2014
NZS 1170.5:2004 (Excl. A1) is cited by Code of Practice for Weathertight Concrete and Concrete Masonry Construction
-
NASH Standard Part 1:2010
NZS 1170.5:2004 (Excl. A1) is cited by NASH Standard - Residential and Low-Rise Steel Framing Part 1 2010 Design Criteria
-
NASH Standard Part 1:2016
NZS 1170.5:2004 (Excl. A1) is cited by NASH Standard Part 1:2016 Design Criteria - Alternative Solution
-
NZS 3101.1:2006 (inc A1, A2)
NZS 1170.5:2004 (Excl. A1) is cited by NZS 3101.1:2006 (inc A1, A2) Concrete structures standard. - Part 1: The design of concrete structures. - SPONSORED.
-
NZS 3101.1:2006 (inc A1, A2, A3)
NZS 1170.5:2004 (Excl. A1) is cited by NZS 3101.1:2006 (inc A1, A2, A3) Concrete structures standard. - Part 1: The design of concrete structures. - SPONSORED. from 30/08/2017
-
NZS 3101.2:2006 (inc A1, A2)
NZS 1170.5:2004 (Excl. A1) is cited by NZS 3101.2:2006 (inc A1, A2) Concrete structures standard. - Part 2: Commentary on the design of concrete structures. - SPONSORED.
-
NZS 3101.2:2006 (inc A1, A2, A3)
NZS 1170.5:2004 (Excl. A1) is cited by NZS 3101.2:2006 (inc A1, A2, A3) Concrete structures standard. - Part 2: Commentary on the design of concrete structures. - SPONSORED.
-
NZS 3106:2009
NZS 1170.5:2004 (Excl. A1) is cited by NZS 3106:2009 Design of concrete structures for the storage of liquids. - SPONSORED
-
NZS 3404 Parts 1 and 2:1997
NZS 1170.5:2004 (Excl. A1) is cited by NZS 3404 Parts 1 and 2:1997 Steel structures standard - SPONSORED
-
NZS 3604:2011
NZS 1170.5:2004 (Excl. A1) is cited by NZS 3604:2011 Timber-framed buildings - SPONSORED
-
NZS 4211:2008
NZS 1170.5:2004 (Excl. A1) is cited by NZS 4211:2008 Specification for performance of windows - SPONSORED
-
NZS 4219:2009
NZS 1170.5:2004 (Excl. A1) is cited by NZS 4219:2009 Seismic performance of engineering systems in buildings - SPONSORED
-
NZS 4223.1:2008
NZS 1170.5:2004 (Excl. A1) is cited by NZS 4223.1:2008 Code of practice for glazing in buildings - Glass selection and glazing - SPONSORED
-
NZS 4229:2013
NZS 1170.5:2004 (Excl. A1) is cited by NZS 4229:2013 Concrete masonry buildings not requiring specific engineering design - SPONSORED
-
NZS 4230:2004
NZS 1170.5:2004 (Excl. A1) is cited by NZS 4230:2004 Design of reinforced concrete masonry structures - SPONSORED
-
NZS 4251.1:2007
NZS 1170.5:2004 (Excl. A1) is cited by NZS 4251.1:2007 Solid plastering - Cement plaster for walls, ceilings and soffits - SPONSORED
-
NZS 4510:2008
NZS 1170.5:2004 (Excl. A1) is cited by NZS 4510:2008 Fire hydrant systems for buildings - SPONSORED
-
NZS 4510:2022
NZS 1170.5:2004 (Excl. A1) is cited by NZS 4510:2022 Fire hydrant systems - SPONSORED
-
NZS 4512:2021
NZS 1170.5:2004 (Excl. A1) is cited by NZS 4512:2021 Fire detection and alarm systems in buildings -SPONSORED
-
NZS 4515:2009
NZS 1170.5:2004 (Excl. A1) is cited by NZS 4515:2009 Fire sprinkler systems for life safety in sleeping occupancies (up to 2000 square metres) - SPONSORED
-
NZS 4541:2007
NZS 1170.5:2004 (Excl. A1) is cited by NZS 4541:2007 Automatic fire sprinkler systems
-
NZS 4541:2013
NZS 1170.5:2004 (Excl. A1) is cited by NZS 4541:2013 Automatic fire sprinkler systems
-
NZS 4541:2020
NZS 1170.5:2004 (Excl. A1) is cited by NZS 4541:2020 Automatic fire sprinkler systems
This resource cites:
NZS 1170.5:2004 (Excl. A1) Structural Design Actions - Part 5: Earthquake design actions - New Zealand - Sponsored.
This document CITES:
NZS 1170.5:2004 (Excl. A1) cites AS/NZS 1170.0:2002 Structural Design Actions - General principles
NZS 1170.5:2004 (Excl. A1) cites AS/NZS 1170.1:2002 (R2016) Structural Design Actions - Permanent, imposed and other actions
NZS 1170.5:2004 (Excl. A1) cites AS/NZS 1170.3:2003 (R2016) Structural Design Actions - Snow and ice actions
NZS 1170.5:2004 (Excl. A1) cites NZS 3101 PARTS 1 AND 2:1995 Concrete structures standard - The design of concrete structures. - SPONSORED