AS 4032.2-2002 Water supply - Valves for the control of hot water supply temperatures. Part 2: Tempering valves and end of line temperature actuated devices
- Abbreviation
- AS 4032.2-2002
- Valid from
- 1/01/2002
- Information provider
- Intertek Inform,
- Author
- Standards Australia
- Information type
- Australian Standard,
- Format
- PDF, HARD COPY,
Description
This Standard specifies requirements for the design, construction, testing and performance of
- a) tempering valves of nominal sizes not larger than DN 32; and
- b) end-of-line temperature-actuated devices of nominal size DN 15, for use with hot water at
- i) continuous operating temperature not exceeding 85C;
- ii) temperature under emergency conditions, not exceeding 99C; and
- iii) continuous working pressure not exceeding 1400 kPa.
The major requirement of the testing procedures is that the device under test does not permit the continuous discharge of water from the outlet in excess of 50C.
Discharges of water with a temperature in excess of this figure, which comply with the specified cumulative time/temperature factors, are acceptable.
This resource is cited by:
AS 4032.2-2002 Water supply - Valves for the control of hot water supply temperatures. Part 2: Tempering valves and end of line temperature actuated devices
This document is CITED BY:
-
AS 4032.3-2004
AS 4032.2-2002 is cited by AS 4032.3-2004 Water supply - Valves for the control of heated water supply temperatures. Part 3: Requirements for field-testing, maintenance or replacement of thermostatic mixing valves, tempering valves and end-of-line temperature control devices