AS 4032.2-2002 Water supply - Valves for the control of hot water supply temperatures. Part 2: Tempering valves and end of line temperature actuated devices

Abbreviation
AS 4032.2-2002
Valid from
1/01/2002

Information provider
Intertek Inform,
Author
Standards Australia
Information type
Australian Standard,
Format
PDF, HARD COPY,


Description

This Standard specifies requirements for the design, construction, testing and performance of

  • a) tempering valves of nominal sizes not larger than DN 32; and
  • b) end-of-line temperature-actuated devices of nominal size DN 15, for use with hot water at
    • i) continuous operating temperature not exceeding 85C;
    • ii) temperature under emergency conditions, not exceeding 99C; and
    • iii) continuous working pressure not exceeding 1400 kPa.

The major requirement of the testing procedures is that the device under test does not permit the continuous discharge of water from the outlet in excess of 50C.

Discharges of water with a temperature in excess of this figure, which comply with the specified cumulative time/temperature factors, are acceptable.

For assistance with locating previous versions, please contact the information provider.
View on Information Provider website
For assistance with locating previous versions, please contact the information provider.
This resource is cited by:

AS 4032.2-2002 Water supply - Valves for the control of hot water supply temperatures. Part 2: Tempering valves and end of line temperature actuated devices

This document is CITED BY:

AS 4032.2-2002 Water supply - Valves for the control of hot water supply temperatures. Part 2: Tempering valves and end of line temperature actuated devices

Description

This Standard specifies requirements for the design, construction, testing and performance of

  • a) tempering valves of nominal sizes not larger than DN 32; and
  • b) end-of-line temperature-actuated devices of nominal size DN 15, for use with hot water at
    • i) continuous operating temperature not exceeding 85C;
    • ii) temperature under emergency conditions, not exceeding 99C; and
    • iii) continuous working pressure not exceeding 1400 kPa.

The major requirement of the testing procedures is that the device under test does not permit the continuous discharge of water from the outlet in excess of 50C.

Discharges of water with a temperature in excess of this figure, which comply with the specified cumulative time/temperature factors, are acceptable.

View on Information Provider website
AS 4032.2-2002 Water supply - Valves for the control of hot water supply temperatures. Part 2: Tempering valves and end of line temperature actuated devices
Description

This Standard specifies requirements for the design, construction, testing and performance of

  • a) tempering valves of nominal sizes not larger than DN 32; and
  • b) end-of-line temperature-actuated devices of nominal size DN 15, for use with hot water at
    • i) continuous operating temperature not exceeding 85C;
    • ii) temperature under emergency conditions, not exceeding 99C; and
    • iii) continuous working pressure not exceeding 1400 kPa.

The major requirement of the testing procedures is that the device under test does not permit the continuous discharge of water from the outlet in excess of 50C.

Discharges of water with a temperature in excess of this figure, which comply with the specified cumulative time/temperature factors, are acceptable.

View on Information Provider website
This resource does not cite any other resources.

AS 4032.2-2002 Water supply - Valves for the control of hot water supply temperatures. Part 2: Tempering valves and end of line temperature actuated devices

This resource does not CITE any other resources.
Feedback