EcoTUFF TPO Roof and Deck Membrane
- Abbreviation
- Appraisal number 792
- Valid from
- 27/05/2020
- Information provider
- BRANZ Limited,
- Information type
- BRANZ Appraisal,
- Format
- PDF,
Description
EcoTUFF TPO Roof and Deck Membrane is a single ply, polyester fabric reinforced, thermoplastic polyolefin (TPO) fully bonded roof waterproofing sheet membrane for building roofs and decks.
Scope
EcoTUFF TPO Roof and Deck Membrane has been appraised as a roof and deck waterproofing membrane on buildings within the following scope:
- the scope limitations of NZBC Acceptable Solution E2/AS1, Paragraph 1.1; or
- the scope limitations of NZBC Acceptable Solution E2/AS1, Paragraph 1.1 with respect to building height and maximum floor plan areas when subject to specific design; and,
- with building structures designed and constructed to meet the requirements of the NZBC; and,
- with substrates of plywood or concrete slab; and,
- with minimum falls for roofs of 1:30 and decks of 1:40; and,
- with decks that have a maximum area of 40 m2; and,
- situated in NZS 3604 Wind Zones, up to, and including Extra High.
EcoTUFF TPO Roof and Deck Membrane has also been appraised for use as a roof and deck waterproofing membrane on specifically designed buildings within the following scope:
- subject to specific structural and weathertightness design; and,
- with substrates of plywood or concrete slab; and,
- situated in specific design wind pressures up to a maximum design differential ultimate limit state (ULS) of 6.0 kPa and,
- with the weathertightness design of junctions for each specific structure being the responsibility of the building designer.
Roofs and decks waterproofed with EcoTUFF TPO Roof and Deck Membrane must be designed and constructed in accordance with the following limitations:
- nominally flat or pitched roofs and decks constructed to drain water to gutters and drainage outlets complying with the NZBC; and,
- with no steps within the deck level, no integral roof gardens and no downpipe direct discharge to the decks; and,
- with the deck membrane continually protected from physical damage by pedestal protection system.
The design and construction of the substrate and movement and control joints is specific to each building, and therefore is the responsibility of the building designer and building contractor and is outside the scope of this Appraisal.