The effects of humidity on gypsum plasterboard used as lateral load bracings for buildings

Abbreviation
SR 399
Valid from
01/06/2018

Information provider
BRANZ Limited
Author
David Carradine
Information type
Study report
Format
PDF

Description

Currently in New Zealand, a major portion of 1 and 2-storey buildings are constructed to NZS 3604:2011  Timber framed buildings using light timber framing with gypsum plasterboard linings serving as the primary lateral load-resisting system.

Due to the nature of the materials comprising plasterboard, environmental moisture levels have the potential to reduce the effectiveness of plasterboard as a structural component. This includes potentially lower earthquake and wind bracing ratings as determined using the P21 test.

This project investigated the relationships between and the performance of plasterboard linings as lateral load-resisting elements in buildings. Testing was conducted on plasterboard at different humidity levels to determine how fastener holding capacity was affected.

Results were considered in the context of humidity levels that would likely be experienced in these low-rise buildings throughout New Zealand.

The results indicated there was some degradation in plasterboard performance at higher humidity levels. However, the decreases were not considered to be significant enough to warrant changes in current test standards and building practices for buildings constructed according to NZS 3604:2011.

For assistance with locating previous versions, please contact the information provider.
Download this resource (PDF, 1.0MB)
For assistance with locating previous versions, please contact the information provider.
This resource is not cited by any other resources.

The effects of humidity on gypsum plasterboard used as lateral load bracings for buildings

This document is not CITED BY any other resources:

The effects of humidity on gypsum plasterboard used as lateral load bracings for buildings

Description

Currently in New Zealand, a major portion of 1 and 2-storey buildings are constructed to NZS 3604:2011  Timber framed buildings using light timber framing with gypsum plasterboard linings serving as the primary lateral load-resisting system.

Due to the nature of the materials comprising plasterboard, environmental moisture levels have the potential to reduce the effectiveness of plasterboard as a structural component. This includes potentially lower earthquake and wind bracing ratings as determined using the P21 test.

This project investigated the relationships between and the performance of plasterboard linings as lateral load-resisting elements in buildings. Testing was conducted on plasterboard at different humidity levels to determine how fastener holding capacity was affected.

Results were considered in the context of humidity levels that would likely be experienced in these low-rise buildings throughout New Zealand.

The results indicated there was some degradation in plasterboard performance at higher humidity levels. However, the decreases were not considered to be significant enough to warrant changes in current test standards and building practices for buildings constructed according to NZS 3604:2011.

Download this resource (PDF, 1.0MB)
The effects of humidity on gypsum plasterboard used as lateral load bracings for buildings
Description

Currently in New Zealand, a major portion of 1 and 2-storey buildings are constructed to NZS 3604:2011  Timber framed buildings using light timber framing with gypsum plasterboard linings serving as the primary lateral load-resisting system.

Due to the nature of the materials comprising plasterboard, environmental moisture levels have the potential to reduce the effectiveness of plasterboard as a structural component. This includes potentially lower earthquake and wind bracing ratings as determined using the P21 test.

This project investigated the relationships between and the performance of plasterboard linings as lateral load-resisting elements in buildings. Testing was conducted on plasterboard at different humidity levels to determine how fastener holding capacity was affected.

Results were considered in the context of humidity levels that would likely be experienced in these low-rise buildings throughout New Zealand.

The results indicated there was some degradation in plasterboard performance at higher humidity levels. However, the decreases were not considered to be significant enough to warrant changes in current test standards and building practices for buildings constructed according to NZS 3604:2011.