AS/NZS 1668.1:1998 The use of ventilation and air conditioning in buildings - Fire and smoke control in multi-compartment buildings
- Abbreviation
- AS/NZS 1668.1:1998
- Amendment
- AS/NZS 1668.1:1998 A1 . - incorporated. Published 21/11/2002.
- Valid from
- 30/06/1991
- Information provider
- Standards New Zealand
- Author
- Standards New Zealand, Standards Australia
- Information type
- New Zealand Standard
Description
This Standard sets out the minimum requirements for the design, construction, installation and commissioning of mechanical ventilation and airconditioning systems for fire and smoke control in multi-compartment buildings.
Scope
This Standard also includes provisions that are applicable to single compartment buildings. Five specific methods of smoke control are defined and the appropriate requirements specified for each.
The Standard does not include requirements for smoke control systems utilizing exhaust from above the hot layer. Requirements for the maintenance of smoke control systems are also not included.
This resource is cited by:
AS/NZS 1668.1:1998 The use of ventilation and air conditioning in buildings - Fire and smoke control in multi-compartment buildings
This document is CITED BY:
-
C/AS1 (Amd 5) (First Edition, Amendment 5)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS1: Buildings with Sleeping (residential) and Outbuildings (Risk Group SH) from 10/04/2012
-
C/AS1 (1st Edition) (First Edition)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS1: Buildings with Sleeping (residential) and Outbuildings (Risk Group SH) from 10/04/2012
-
C/AS1 (Amd 2) (Amendment 2)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS1: Buildings with Sleeping (residential) and Outbuildings (Risk Group SH) from 10/04/2012
-
C/AS1 (Amd 4) (First edition, amendment 4)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS1: Buildings with Sleeping (residential) and Outbuildings (Risk Group SH) from 10/04/2012
-
C/AS1 (Amd 1, Errata 1) (Amendment 1, Errata 1)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS1: Buildings with Sleeping (residential) and Outbuildings (Risk Group SH) from 10/04/2012
-
C/AS1 (Amd 3) (Amendment 3)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS1: Buildings with Sleeping (residential) and Outbuildings (Risk Group SH) from 10/04/2012
-
C/AS2 (Amd 2) (First Edition, Amendment 2)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS2: Buildings other than Risk Group SH from 27/06/2019
-
C/AS2 (First Edition, Amd 1 (Errata 1) (First Edition, Amendment 1 (Errata1 - 22/10/2019))
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS2: Buildings other than Risk Group SH from 27/06/2019
-
C/AS2 (First Edition)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS2: Buildings with Sleeping (non institutional) (Risk Group SM) from 10/04/2012
-
C/AS2 (Amendment 2)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS2: Buildings with Sleeping (non institutional) (Risk Group SM) from 10/04/2012
-
C/AS2 (First edition, amendment 4)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS2: Buildings with Sleeping (non institutional) (Risk Group SM) from 10/04/2012
-
C/AS2 (Amendment 1, Errata 1)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS2: Buildings with Sleeping (non institutional) (Risk Group SM) from 10/04/2012
-
C/AS2 (Amendment 3)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS2: Buildings with Sleeping (non institutional) (Risk Group SM) from 10/04/2012
-
C/AS3 (First Edition)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS3: Buildings Where Care or Detention is Provided (Risk Group SI) from 10/04/2012
-
C/AS3 (First edition, amendment 4)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS3: Buildings Where Care or Detention is Provided (Risk Group SI) from 10/04/2012
-
C/AS3 (Amendment 2)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS3: Buildings Where Care or Detention is Provided (Risk Group SI) from 10/04/2012
-
C/AS3 (Amendment 1, Errata 1.)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS3: Buildings Where Care or Detention is Provided (Risk Group SI) from 10/04/2012
-
C/AS3 (Amendment 3)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS3: Buildings Where Care or Detention is Provided (Risk Group SI) from 10/04/2012
-
C/AS4 (Amendment 2)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS4: Buildings with Public Access and Educational Facilities (Risk Group CA) from 10/04/2012
-
C/AS4 (Amendment 1, Errata 1)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS4: Buildings with Public Access and Educational Facilities (Risk Group CA) from 10/04/2012
-
C/AS4 (Amendment 3)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS4: Buildings with Public Access and Educational Facilities (Risk Group CA) from 10/04/2012
-
C/AS4 (First edition, amendment 4)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS4: Buildings with Public Access and Educational Facilities (Risk Group CA) from 10/04/2012
-
C/AS4 (First Edition)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS4: Buildings with Public Access and Educational Facilities (Risk Group CA) from 10/04/2012
-
C/AS5 (First edition, amendment 4)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS5: Buildings used for Business, Commercial and Low Level Storage (Risk Group WB) from 10/04/2012
-
C/AS5 (Amendment 1, Errata 1.)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS5: Buildings used for Business, Commercial and Low Level Storage (Risk Group WB) from 10/04/2012
-
C/AS5 (Amendment 3)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS5: Buildings used for Business, Commercial and Low Level Storage (Risk Group WB) from 10/04/2012
-
C/AS5 (First Edition)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS5: Buildings used for Business, Commercial and Low Level Storage (Risk Group WB) from 10/04/2012
-
C/AS5 (Amendment 2)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS5: Buildings used for Business, Commercial and Low Level Storage (Risk Group WB) from 10/04/2012
-
C/AS6 (First Edition)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS6: Buildings used for High Level Storage and Other High Risk Purposes (Risk Group WS) from 10/04/2012
-
C/AS6 (Amendment 3.)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS6: Buildings used for High Level Storage and Other High Risk Purposes (Risk Group WS) from 10/04/2012
-
C/AS6 (Amendment 2)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS6: Buildings used for High Level Storage and Other High Risk Purposes (Risk Group WS) from 10/04/2012
-
C/AS6 (First edition, amendment 4)
AS/NZS 1668.1:1998 is cited by Acceptable Solution C/AS6: Buildings used for High Level Storage and Other High Risk Purposes (Risk Group WS) from 10/04/2012
-
F7/AS1 (Amd 6) (Third Edition, Amendment 6)
AS/NZS 1668.1:1998 is cited by Acceptable Solution F7/AS1: Warning Systems from 1/12/2000
-
F7/AS1 (Third Edition, Amendment 7)
AS/NZS 1668.1:1998 is cited by Acceptable Solution F7/AS1: Warning Systems from 1/12/2000
-
C/VM1 (Amd 5) (First Edition, Amendment 5)
AS/NZS 1668.1:1998 is cited by Verification Method C/VM1: Solid Fuel Appliances from 5/11/2020
-
C/VM1 (Amd 4) (First Edition, Amendment 4)
AS/NZS 1668.1:1998 is cited by Verification Method C/VM1: Solid Fuel Appliances from 1/02/2013
-
AS 1668.2-2012
AS/NZS 1668.1:1998 is cited by AS 1668.2-2012 The use of ventilation and airconditioning in buildings - Part 2: Mechanical ventilation in buildings
-
AS 4254.2-2012
AS/NZS 1668.1:1998 is cited by AS 4254.2-2012 Ductwork for air-handling systems in buildings. Part 2: Rigid duct
This resource cites:
AS/NZS 1668.1:1998 The use of ventilation and air conditioning in buildings - Fire and smoke control in multi-compartment buildings
This document CITES:
New Zealand Standards
-
AS/NZS 3013:1995
AS/NZS 1668.1:1998 cites AS/NZS 3013:1995 Electrical installations - Classification of the fire and mechanical performance of wiring systems
-
AS/NZS 3103:1993
AS/NZS 1668.1:1998 cites AS/NZS 3103:1993 Approval and test specification - Electric room heaters
-
AS/NZS 3179:1993
AS/NZS 1668.1:1998 cites AS/NZS 3179:1993 Approval and test specification - Refrigerated room air conditioners
-
NZS 2139:1967
AS/NZS 1668.1:1998 cites NZS 2139:1967 Specification for heat actuated fire detectors
-
NZS 4512:1994
AS/NZS 1668.1:1998 cites NZS 4512:1994 Fire alarm systems in buildings - SPONSORED
-
NZS/AS 1530.1:1994 (R2016)
AS/NZS 1668.1:1998 cites NZS/AS 1530.1:1994 (R2016) Methods for fire tests on building materials, components and structures - Part 1: Combustibility test for materials
Australian Standards
-
AS 1324.1-1996
AS/NZS 1668.1:1998 cites AS 1324.1-1996 Air filters for use in ventilation and airconditioning - Part 1: Application performance and construction
-
AS 1530.3-1982
AS/NZS 1668.1:1998 cites AS 1530.3-1982 Methods for fire tests on building materials and structures - Part 3: Test for early fire hazard properties of materials
-
AS 1530.4-1997
AS/NZS 1668.1:1998 cites AS 1530.4-1997 Methods for fire tests on building materials components and structures - Fire-resistance test of elements of building construction
-
AS 1603.1-1997 (R2016)
AS/NZS 1668.1:1998 cites AS 1603.1-1997 (R2016) Automatic fire detection and alarm systems - Part 1: Heat detectors
-
AS 1603.13-1998 (R2016)
AS/NZS 1668.1:1998 cites AS 1603.13-1998 (R2016) Automatic fire detection and alarm systems - Heat detectors - Part 13: Duct Sampling units
-
AS 1603.2-1997 (R2016)
AS/NZS 1668.1:1998 cites AS 1603.2-1997 (R2016) Automatic fire detection and alarm systems - Part 2: Point type smoke detectors
-
AS 1603.8-1996 (R2016)
AS/NZS 1668.1:1998 cites AS 1603.8-1996 (R2016) Automatic fire detection and alarm systems. Part 8: Multi-point aspirated smoke detectors
-
AS 1668.2-1991
AS/NZS 1668.1:1998 cites AS 1668.2-1991 The use of mechanical ventilation and air-conditioning in buildings - Part 2: Mechanical ventilation for acceptable indoor-air quality
-
AS 1670.1-1995
AS/NZS 1668.1:1998 cites AS 1670.1-1995 Fire detection, warning, control and intercom systems - System design, installation and commissioning - Part 1: Fire
-
AS 1682.1-1990
AS/NZS 1668.1:1998 cites AS 1682.1-1990 Fire dampers - Part 1: Specification
-
AS 1682.2-1990
AS/NZS 1668.1:1998 cites AS 1682.2-1990 Fire dampers - Part 2: Installation
-
AS 1735.2-1993
AS/NZS 1668.1:1998 cites AS 1735.2-1993 Lifts escalators and moving walks - Passenger and goods lifts - Part 2: Electric
-
AS 2106-1980
AS/NZS 1668.1:1998 cites AS 2106-1980 Methods for the determination of the flashpoint of flammable liquids (closed cup)
-
AS 2118.1-1995
AS/NZS 1668.1:1998 cites AS 2118.1-1995 Automatic fire sprinkler systems - Part 1: Standard
-
AS 2484.1-1990 (R2016)
AS/NZS 1668.1:1998 cites AS 2484.1-1990 (R2016) Fire - Glossary of terms - Part 1: Fire tests
-
AS 3102-1983
AS/NZS 1668.1:1998 cites AS 3102-1983 Approval and test specification for electric duct heaters
-
AS 4072.1-1992
AS/NZS 1668.1:1998 cites AS 4072.1-1992 Components for the protection of openings in fire-resistant separating elements - Service penetrations and control joints
-
AS 4254-1995
AS/NZS 1668.1:1998 cites AS 4254-1995 Ductwork for air-handling systems in buildings
-
AS 4260-1997
AS/NZS 1668.1:1998 cites AS 4260-1997 (R2018) High efficiency particulate air (HEPA) filters - Classification, construction and performance
-
AS 4428.1-1998 (R2016)
AS/NZS 1668.1:1998 cites AS 4428.1-1998 (R2016) Fire detection, warning, control and intercom systems - Control and indicating equipment Fire - Part 1: Fire
-
AS 4428.7-1999 (R2016)
AS/NZS 1668.1:1998 cites AS 4428.7-1999 (R2016) Fire detection, warning, control and intercom systems - Control and indicating equipment - Part 7: Air-handling fire mode control panel
-
AS 4429(Int)-1996
AS/NZS 1668.1:1998 cites AS 4429(Int)-1996 Methods of test and rating requirements for smoke-spill fans
Other
-
ASHRAE Handbook - Fundamentals 1997
AS/NZS 1668.1:1998 cites ASHRAE Handbook - Fundamentals 1997
-
ASHRAE Handbook - HVAC Applications 1995
AS/NZS 1668.1:1998 cites ASHRAE Handbook - HVAC Applications 1995
-
Design of smoke management systems
AS/NZS 1668.1:1998 cites Design of smoke management systems